Cable fault types and fault location methods

Enerji Test Servis · Updated:

To locate a cable fault quickly you first need to know its type, because each type calls for a different method. Here are the main cable fault types and how each is found, in plain language.

Quick answer
  • First insulation is measured and the fault type is identified.
  • Then the distance is found with a TDR or the arc reflection method.
  • Finally the exact spot is pinpointed on the route by acoustic or step-voltage methods.

Fault types

  • Low-resistance fault (short circuit): conductors are shorted to each other or to the screen.
  • Open circuit: a conductor is broken.
  • High-resistance fault: insulation is weakened but not fully shorted.
  • Intermittent (flashing) fault: breaks down only under high voltage and is invisible to normal measurement.
  • Sheath fault: outer insulation is damaged and moisture gets in.

Time domain reflectometer (TDR)

A short pulse is sent into the cable and the return time of the reflection is measured. For low-resistance faults — shorts and opens — the TDR shows the distance accurately. For high-resistance faults it is not enough on its own.

Arc reflection and surge generator

For high-resistance and intermittent faults, a surge generator creates a short arc at the fault. While the arc burns the fault becomes low-resistance, so the reflectometer can “see” it. Our SPC20 system has a multi-impulse arc unit.

Pinpointing on the route

Once the distance is known, the spot is found on the route: each surge produces a sound at the fault, which an acoustic receiver picks up. Sheath faults are pinpointed with the step-voltage method. This step keeps excavation to a minimum.

Step by step: how to find a cable fault. Service: cable fault location.

Need this service?

Cable fault location — Enerji Test Servis

Learn more →

FAQ

Which fault is hardest to find?

High-resistance and intermittent faults: they do not show up in normal measurement and need a surge generator and arc reflection.

How accurate is it?

The final spot is pinpointed acoustically on the route, so digging usually happens in one place.

Which cables do you test?

Underground and exposed power cables.