How to find a cable fault: 4 steps

Enerji Test Servis · Updated:

When an underground cable fails, the costliest mistake is digging blind: every metre of asphalt opened in the wrong place costs time and money. A professional laboratory first measures the fault with instruments, then pinpoints it on the surface, and only then does digging start. Here is how the process works, step by step.

Quick answer
  • First the fault type is identified: short circuit, open circuit or a high-resistance (intermittent) fault.
  • Then a TDR shows the distance from the cable end to the fault. High-resistance faults need the arc reflection method.
  • Finally the exact spot is found on the surface by acoustic pinpointing, and digging happens only there.

1. Diagnosis: the fault type

The cable is disconnected and each core is tested with a megohmmeter. The result puts the fault into one of three types:

  • Low-resistance (short circuit): a core is connected directly to earth or another core.
  • Open circuit: a core is broken.
  • High-resistance or intermittent: the insulation is damaged but only breaks down at high voltage. This is the hardest case.

This diagnosis decides which method comes next.

2. TDR: distance to the fault

A time-domain reflectometer (TDR) sends a short pulse into the cable. When the pulse reaches the fault it is reflected back. The instrument measures the return time and, knowing the pulse velocity in the cable, calculates the distance: L = v·t / 2. The fault shows up as a step on the trace.

This works well for short circuits and open circuits. A standard TDR cannot "see" a high-resistance fault.

3. High-resistance faults: arc reflection

Here a high-voltage impulse is applied to the cable. An arc forms briefly at the fault, making it low-resistance for that moment. The TDR captures exactly that moment and shows the distance. Our SPC20 system uses a multiple-impulse arc mode: several measurements are compared, so the result is more reliable.

4. The exact spot: acoustic pinpointing

Even with the distance known, cable routes are rarely straight. So the last stage is done on the surface:

  • A surge generator sends repeated impulses into the cable, causing a discharge at the fault each time.
  • A ground sensor (our PP20) picks up the sound of the discharge and its electromagnetic signal.
  • The point where the time gap between the two signals is smallest is directly above the fault.

As a result, digging is usually accurate to within a few tens of centimetres, and only where needed.

After the repair

Once the joint is installed, the cable must be tested again: insulation is measured and, if needed, a high-voltage test is carried out. The result is recorded in a test report.

Need this service?

Cable fault location — Enerji Test Servis

Learn more →

FAQ

How long does fault location take?

It depends on cable length, fault type and whether the route is known. Simple cases take a few hours, complex ones a day.

What if there is no cable route drawing?

We first trace the route with a cable locator, then locate the fault.

Does the whole cable need replacing?

Usually not. The damaged section is cut out and joined. If the cable is old and faults keep recurring, replacement may be more economical.

Do you provide a document afterwards?

Yes, the measurements and the post-repair test are recorded in a test report.

Sources

Request a measurement

Tell us about your site: our engineer will agree scope and price.