Insulation resistance is measured with a megohmmeter (insulation tester): it applies a DC voltage and calculates resistance from the leakage current. Beyond a single reading, how it changes over time — PI and DAR — shows whether insulation is wet or contaminated.
- The test voltage is chosen by the equipment's rated voltage.
- PI = resistance at 10 minutes / resistance at 1 minute.
- DAR = resistance at 60 seconds / resistance at 30 seconds.
Choosing the test voltage
The voltage should match the equipment's rating: too low will not reveal weak spots, too high stresses insulation needlessly. IEEE 43 recommends, for example, 500 V for equipment up to 1000 V, 1000–2500 V for 2.5–5 kV and 2500–5000 V for 5–12 kV. Limits for cables and installations are given in the PUE and operating rules; table: insulation resistance limits.
Polarization index (PI)
After the voltage is applied, resistance rises over time in good insulation but barely changes in wet or dirty insulation. PI is the ratio of the 10-minute reading to the 1-minute reading. General guide: below 1 dangerous, 1–2 questionable, 2–4 good, above 4 excellent.
Dielectric absorption ratio (DAR)
DAR is a shorter test: the 60-second reading divided by the 30-second reading. A value below 1.25 calls for attention, above 1.6 is considered good. DAR is quick; PI is more reliable.
Measuring correctly
- The equipment is de-energised and discharged beforehand.
- Temperature is recorded, because resistance depends strongly on it.
- If surface leakage is suspected, the guard terminal is used.
- After the test the equipment is discharged again.
Service: insulation resistance testing.
Insulation tests — Enerji Test Servis
FAQ
When are PI and DAR needed?
For high-capacitance equipment — motors, generators, transformers, long cables — a single reading can be misleading.
How does temperature affect results?
Insulation resistance falls as temperature rises, so temperature is always recorded for comparison.
Is megohmmeter testing dangerous?
The equipment must be de-energised and discharged; the test should be done by an experienced specialist.
What document do you issue?
A test report from an accredited laboratory (AZS ISO/IEC 17025:2020).